37.88→33.78 °C
Empty channel → 7.5 mm insertPOROUS MEDIA / HYDROTHERMAL PERFORMANCE
Where the flow goes.
Where the heat stays.
A heated channel with a copper porous insert

Porous-layer height, permeability and flow rate change both the temperature pattern and pressure demand. This study follows the local hotspots that an average can hide.
THE ENGINEERING QUESTION
Does a cooler average
mean a cooler hotspot?
At ReH = 500 and DaH = 10⁻⁴, the 7.5 mm insert lowers mean fluid-side heated-wall temperature while raising its local maximum. Much of the water bypasses the porous layer through the remaining clear gap.
42.08→58.76 °C
The hotter peak lies downstream of the insert.These are fluid-side heated-wall temperatures in an idealized numerical channel. The prescribed wall heat enters the fluid phase; a separate heater plate is not modelled.
MODEL & METHOD
A clear geometry.
Two phase temperatures.
A 1 m planar channel contains a 200 mm porous segment. Separate energy equations let water and copper have different local temperatures: local thermal non-equilibrium, or LTNE.

Physical assumptions
- Fluid
- Water, 300 K at inlet; steady, laminar and constant properties.
- Heating
- 5,000 W/m² prescribed on the fluid side of x = 0–300 mm.
- Porosity
- 0.95, with copper conductivity 390 W/(m·K).
- Coupling
- Interfacial area density 9,308 m⁻¹ and heat-transfer coefficient 10,000 W/(m²·K).
- Outlet
- 0 Pa average relative static pressure; 1 atm reference.
Controlled comparisons
- Height: 0, 2.5, 5, 7.5 and 10 mm at ReH = 500 and DaH = 10⁻⁴ for porous cases.
- Permeability: DaH = 10⁻⁵, 10⁻⁴ and 10⁻³ at ReH = 500 and Hp = 5 mm.
- Flow: ReH = 250, 500, 750 and 1,000 at Hp = 2.5 mm and DaH = 10⁻⁴.
ReH = ρUinH/μ; DaH = K/H². Both use the 10 mm channel height. The three comparisons share ten unique cases.
EXPLORE THE SAVED RESULTS
Change one parameter.
Read both consequences.
Select a controlled comparison and a case. Pressure differences use x = 0–300 mm throughout this page.
ReH = 500 · DaH = 10⁻⁴ for porous cases
Thermal resistance uses each case’s actual integrated heat input. Hydraulic power is a static-pressure fluid-power proxy for the modelled slice.
Height: temperature and pressure
| Insert height | Mean wall °C | Peak wall °C | Peak resistance K/W | Pressure difference Pa · 0–300 mm | Flow through porous layer % at x = 150 mm |
|---|---|---|---|---|---|
| Empty | 37.88 | 42.08 | 101.53 | 2.15 | — |
| 2.5 mm | 37.23 | 49.98 | 159.49 | 3.90 | 0.177 |
| 5 mm | 35.97 | 54.00 | 187.21 | 12.82 | 0.644 |
| 7.5 mm | 33.78 | 58.76 | 220.07 | 78.04 | 5.134 |
| 10 mm | 29.94 | 35.78 | 61.56 | 1204.00 | 100.000 |
THE FULL-HEIGHT TRADEOFF
39.4% lower peak resistance.
About 559× the pressure difference.
At the same inlet flow, full filling removes the clear bypass gap and improves the selected thermal metric relative to the empty channel. The pressure cost is substantial over the 300 mm study region.
This comparison does not establish a preferred design at equal pumping power. The model represents the specified porous assumptions, without calibration to a particular foam.
Metric definitions & heat-input correction
Peak resistance: (maximum fluid-side heated-wall temperature − inlet temperature) / actual Q. Values refer to the 0.1 mm modelled width.
Actual heat input: 0.150 W for the empty channel; 0.145 W for porous cases, including porosity-weighted heating of the porous fluid. Identical nominal heat flux therefore gives 3.33% less total heat in porous cases.
Pressure: area-averaged static pressure at x = 0 minus x = 300 mm. The original full-channel values span 1 m and must be compared separately.
Hydraulic-power proxy: this static-pressure difference × native inlet volumetric flow. It excludes pump efficiency and other circuit components.
Porous flow fraction: absolute net mass flow inside the porous section / absolute net mass flow across the whole section, at x = 150 mm. It is a local flow split.
Mean wall temperature: geometric-area-weighted fluid-wall temperature over the heated segments. Native wall extrema supply the peaks.
SPATIAL RESULTS
Follow the bypass.
Find the downstream hotspot.
Partial-height layers redirect flow into the clear gap. At the insert midpoint, only 0.177%, 0.644% and 5.134% of net flow crosses the 2.5, 5 and 7.5 mm porous layers.


Permeability and bypass
At 5 mm height, increasing permeability from 10⁻⁹ to 10⁻⁷ m² increases the midpoint porous flow fraction from 0.070% to 4.543%. The flow split and pressure response describe different parts of the tradeoff.
Flow and pressure demand
At 2.5 mm height, increasing ReH from 250 to 1,000 lowers peak temperature rise by 20.5% while increasing the hydraulic-power proxy over x = 0–300 mm by about 27.4 times.

NUMERICAL EVIDENCE
Converged calculations.
Defined physical limits.
The selected cases use 540,000 hexahedral cells and staged flow and thermal solutions. The thermal stage freezes the flow solution accepted at its 10⁻⁵ RMS target. Retained logs allow residual convergence and conservation to be checked separately.

WHAT THE CHECKS SUPPORT
A traceable numerical comparison
- Each selected stage exited successfully with a saved result file.
- Actual heat input and native wall extrema are retained in the comparisons.
- Original field exports and editable figures support the spatial interpretation.
- Separate water/copper temperatures are evaluated at colocated positions.
WHAT STILL NEEDS WORK
Sensitivity and physical validation
- Mesh independence and a physical benchmark remain open.
- The porous resistance model and fixed interphase coupling need sensitivity checks.
- The incomplete parameter matrix does not establish a global optimum.
- A specified foam and hardware design would require calibration and revised boundary conditions.
CONSERVATION AND SAMPLING
Residuals do not settle every check.
The section sensible-heat closure, [Q − ṁcₚ(Tb,300 − Tin)] / Q, reaches −2.36% at 5 mm and DaH = 10⁻⁵, and −2.10% at 5 mm and DaH = 10⁻⁴. These differences need review. Maximum section mass-flow deviation is about 0.063% across the thirteen reduced-data cases.
A finer interpolation changes mean local Nusselt number by 1.6–11.9%, while overall Nusselt number changes by less than 0.16%. This checks postprocessing sampling; it is not a mesh refinement study.
Small phase averages can hide local differences

LTNE enables different phase temperatures. A direct comparison with local thermal equilibrium (LTE) is still needed to measure its effect on design conclusions. This update reuses the saved simulations.
REPORT & SOURCE DATA
The complete study,
ready to review.
A fresh illustrated portfolio report connects geometry, model assumptions, original scientific figures and verified comparisons. Editable sources and detailed provenance are preserved in the project library.
Porous media in a heated channel · 9 pages ↗